End to End Testing (E2E): 33kV Cable & T/L Protection

Home » Blogs » End to End Testing (E2E): 33kV Cable & T/L Protection

In the high-stakes environment of power system commissioning, testing components in isolation is a recipe for disaster. To ensure a 33kV feeder or a high-voltage transmission line is truly secure, engineers rely on End to End Testing (E2E).

This is the only method to prove that the “Local” and “Remote” ends of a protection scheme act as a single, unified defense against faults.

What Is End to End (E2E) Testing in Line Protection?

End to End testing (E2E) is a synchronized functional verification of line protection schemes (87L & 21) between two substations. Using GPS-timed injection (Omicron CMGPS 588), it validates the entire chain: relays, communication links (FOC/PLC), and tripping logic to ensure stability during through-faults and instantaneous clearing during internal faults.

⚡ 1. Why E2E Testing is Non-Negotiable

Standard secondary injection proves a relay works, but E2E testing proves the system works. It targets four critical areas:

  • Communication Integrity: Is the fiber optic (FOC) or PLC link exchanging data without lag?
  • Time Synchronization: Are both relays “seeing” the power cycle at the exact same microsecond?
  • Stability: Will the relay remain “blind” to external faults (through-faults)?
  • Sensitivity: Will it trip instantly for internal faults, even if fed from only one side?

⚙️ 2. Core Protection Schemes Covered

Line Differential Protection (87L / 87CH)

This scheme relies on Kirchhoff’s Law. The relay at Substation A compares its current vector with the vector from Substation B.

  • Stability Logic: During normal load, the vectors cancel out (I_{diff} |approx 0).
  • Fault Logic: During an internal fault, the vectors sum up, triggering a trip.

Distance Protection (21)

E2E testing is vital for communication-aided distance schemes (POTT, PUTT, or blocking).

  • Zone 1 & 2 Reach: Verifies that a fault at the “far end” of the line (90% reach) correctly triggers an instantaneous “permissive trip” rather than waiting for a Zone 2 time delay.

🧰 3. The Professional Tool Kit

To match the precision required by vendors like Siemens (SIPROTEC 5) or ABB (Relion), you need the following:

  • Injection Units: OMICRON CMC 356 or Megger SVERKER.
  • GPS Sync: CMGPS 588. This is the “heart” of the test, ensuring 1 ms timing accuracy between sites.
  • Software: Siemens DIGSI 5 or vendor-specific IED tools to monitor real-time I_{diff} and I_{rest} values.

🧾 4. Step-by-Step Field Procedure

Phase 1: Communication & Mapping Verification

Before injecting current, you must verify the “handshake” signals identified in your Binary I/O (BI/BO) and LED tables:

  1. Channel Check: Disconnect the fiber patch cord. The relay must immediately flag a “COM ALM” or “Link Failure.”
  2. Signal Mapping: Verify specific signals like “87CH Healthy,” “CB Service,” and “Remote Trip Received” are mapping correctly to the SCADA and local LEDs.

Phase 2: The Stability Test (Case 1 vs. Case 2)

  • Case 1 (Site Stability): If primary current is available, use it to confirm the relays see “through-load.”
  • Case 2 (GPS-Simulated): Inject current at both ends simultaneously.
    • Settings: Substation A at 0 degree | Substation B at 180 degrees.
    • Requirement: The differential current must satisfy the following:
      I_{diff} = |I Local + I Remote| approx 0
    • Goal: The relay stays stable (no trip).

Phase 3: The Sensitivity & Timing Test

  • Settings: Substation A at 0 degree | Substation B at 0 degree (in-phase).
  • Distance Test: Simulate a fault at 50% line impedance.
  • Requirement: Both relays must issue a TRIP command.
  • Timing: The signal exchange (inter-trip) must be confirmed within <10 ms.

📊 5. Key Indicators for Acceptance

Based on actual field commissioning formats, your results should align with this table:

Test ParameterExpected ResultSignificance
FOC HealthAlarms ClearComm link reliability.
Stability @ 2 I_nI_{diff} < 0.1 \times I_{n}No false trips during motor starts/external faults.
Sensitivity TripRelay Trips @ SetpointFast fault clearing.
Remote Trip SignalHigh/PulsedInter-station logic is working.
GPS Lock“3D Lock” / 4+ SatellitesAccuracy of the test data.

🧠 6. Safety & Best Practices

  1. Isolation: Use test switches (like ABB FT-1) to ensure you don’t accidentally trip the entire grid during the simulation.
  2. Polarity Check: Reversed CT polarities are the #1 cause of E2E failure. Always perform a wiring check before the GPS test.
  3. Inhibit Tripping: Use the “Trip Inhibit” binary input during initial logic checks to protect the circuit breaker from unnecessary wear.

Final words:

E2E testing is the gold standard for 33kV and transmission line protection. By combining GPS-synchronized injection with rigorous binary I/O mapping, engineers ensure that the distance and differential schemes provide maximum reliability. Whether you are using Siemens, ABB, or GE relays, the physics remains the same: Synchronize, Inject, and Verify.

What is End to End Testing ( E2E) in line protection.?

E2E testing is a GPS-synchronized functional verification of line protection schemes — typically 87L (differential) and 21 (distance) — carried out simultaneously between two substations at opposite ends of a feeder or transmission line.
Unlike standard secondary injection, which only proves that a single relay functions, E2E testing validates the entire protection chain: the relays at both ends, the communication link (fiber optic or PLC), and the inter-tripping logic — all working together as a single unified defense.

Which protection schemes does E2E testing cover?

Line Differential (87L / 87CH): Both ends inject current simultaneously. The relay compares the local current vector with the remote vector received over the communication link. During a stability test the vectors cancel (I_diff ≈ 0); during a sensitivity test they add up, producing a trip.
Distance Protection (21)—aided schemes: E2E verifies that communication-aided modes like POTT, PUTT, or blocking operate correctly. A fault simulated at the remote end (e.g., 90% reach) must trigger an instantaneous permissive trip instead of waiting for the Zone 2 time delay.

Why is the CMGPS 588 described as the heart of the best?

The CMGPS 588 locks the OMICRON injection unit to GPS satellite time, giving a timing accuracy of ≤1 ms. Without this synchronization, the two injection units would operate on independent clocks and introduce an artificial phase shift between the local and remote current vectors.
This would make a properly wired and stable differential scheme appear to have a differential current—producing either a false trip or a misleading pass. For the test result to be meaningful, the GPS lock must show ” 3D Lock” with 4 or more satellites at both ends before any current is injected.

What angle settings are used in the stability test and why?

For the stability test (through-fault simulation), the injection angles are set as follows:
Substation A: 0°
Substation B: 180°
The 180° phase opposition is intentional. It mimics current flowing into the line at one end and out at the other—exactly what happens during a normal load or an external fault. Under this condition, Kirchhoff’s current law dictates that the vector sum equals zero: I_diff = |I_Local + I_Remote| ≈ 0. The relay must remain stable (no trip). This is also called Case 2 (GPS-Simulated), used when primary load current is not available.

What angle settings are used in the sensitivity test?

For the sensitivity test (internal fault simulation), both ends inject at the same angle:
Substation A: 0°
Substation B: 0°
With currents in phase, they add rather than cancel: I_diff = |I_Local + I_Remote| >> I_pickup. This simulates an internal fault where current flows into the protected zone from both ends. The expected outcome is a TRIP command from both relays with the inter-trip signal exchanged within less than 10 ms. A fault at 50% of the line impedance is a typical test point.

What is the difference between Case1 and Case2 in the stability test?

Case 1 (Live primary current): If the feeder is energized and carrying load, primary current already provides a real through-load condition. Both relays see actual system currents, and the differential element must stay stable without any test injection.
Case 2 (GPS-simulated): Used when the feeder is de-energized or the primary current is unavailable. The OMICRON units inject at 0°/180° to simulate through-load artificially, providing the same functional verification without live primary current.

What are the acceptance criteria for an E2E test?

FOC health: All communication alarms clear with no latency warnings.
Stability @ 2×In: Differential current I_diff < 0.1 × I_n — no false trip during motor starts or external faults.
Sensitivity trip: Both relays trip at the configured pickup setpoint.
Remote trip signal: The Remote Trip Received” binary output shows High or Pulsed—confirming inter-station logic is functional.
GPS lock quality: “3D Lock” with 4 or more satellites at both ends before and during the test.
Inter-trip timing: Signal exchange confirmed within <10 ms.

How do you prevent accidentally tripping the grid during an E2E test?

Test switches: Use ABB FT-1 or equivalent test terminal blocks to isolate the relay’s trip output from the actual circuit breaker trip coil during the initial logic verification stages.
Trip Inhibit binary input: Activate the relay’s “Trip Inhibit” binary input during all binary I/O mapping checks. This allows the injection and logic to be verified without energizing the trip circuit, preventing unnecessary CB wear or an unintended trip.
Staged verification: Only remove isolation and inhibit functions once signal mapping, communication, and polarity have been confirmed at both ends.

Explore the world of elctrical substation faults and troubleshooting. Our blogs provides valueable insights,tips and guides to help you understand and address various issues in substation operations.

Follow me

© 2026 SubstationFaults.com — All Rights Reserved

Built with ⚡ by Fazli Wahid

Scroll to Top