Transformer Explosion: Causes, Warning Signs & Prevention

Home » Blogs » Transformer Explosion: Causes, Warning Signs & Prevention

What Causes Transformer Explosions?

Transformer explosions are extremely dangerous. When a transformer fails, it can explode violently and suddenly. These explosions destroy equipment worth millions of dollars, cut off power to thousands of homes, and put lives at risk.

The Physics behind Transformer Explosions

When low impedance faults develop inside transformers, electrical arcing vaporizes the insulating oil, generating pressurized gas bubbles. The pressure difference between expanding gas and surrounding liquid creates dynamic pressure peaks that propagate through the tank, building static pressure until the structure ruptures catastrophically.

What Does Transformer Explosion Sound Like? The Signature Sound of Failure

A blown transformer produces a loud bang or boom often mistaken for gunshots or explosions, caused by arc flash and sudden pressure release that creates a percussive, concussive sound audible from significant distances.

The sound sequence typically unfolds in milliseconds:

Before the explosion: Increased humming or buzzing as the transformer struggles under electrical stress, followed by sizzling or crackling sounds from internal arcing.

During the explosion: A sharp, loud bang similar to firecrackers or small explosions, often accompanied by popping or whining as pressure builds and releases.

After the explosion: Continuing crackling from electrical discharge, hissing from escaping gases, and the roar of burning oil if fire ignites.

In December 2018, a massive transformer explosion in Queens turned the night sky blue, with the sound described as “like a cannon or bomb,” prompting over 300 emergency calls reporting gunshots or explosions.

Why Are Transformer Explosions So Bright? The Science of Light

The Spectacular Visual Display

The bright light from transformer explosions can be visible from miles away, depending on the transformers power output. This intense luminosity results from multiple simultaneous phenomena:

Arc Flash Luminescence: When electrical current jumps across gaps, it ionizes air molecules and vaporized oil, creating plasma that emits intense white-blue light. The excessive voltage creates dramatic electrical arcing and sparks, producing a dazzling light show akin to fireworks.

Color Variations Explained:

  • Blue-Green Light: Results from incomplete combustion of carbon monoxide or chemical reactions involving copper components within the transformer
  • Orange Flames: Standard combustion of mineral oil and insulation materials
  • Bright White Flash: Initial arc flash from high-energy electrical discharge

The famous Queens explosion illuminated the entire neighborhood in an eerie turquoise glow, described as bright as daytime but in green-blue color, with no accompanying fireworks noise.

What Happens If a Transformer Blows? Immediate and Long-Term Effects

The Cascade of Consequences

When a transformer blows, it typically results in a loud explosion accompanied by a bright flash of light, possibly fire, and power outages in the surrounding area.

Immediate Impacts:

  1. Power Disruption: Thousands of homes and businesses lose electricity instantly. However, a blown transformer typically affects a limited section of the distribution network, not an entire city.
  2. Fire Hazards: Transformers contain thousands of gallons of highly flammable mineral oil. When this oil heats up too much, it can ignite and spread quickly, especially near trees, buildings, or power lines.
  3. Downed Power Lines: If wires fall to the ground, they can still be live and extremely dangerous, with electricity capable of traveling through the ground or metal objects.
  4. Physical Damage: The explosion throws burning oil, metal fragments, and debris across surrounding areas, damaging nearby equipment and infrastructure.
  5. Environmental Contamination: Oil spills pollute soil and water sources, while toxic gases release into the atmosphere.

Long-Term Consequences:

  • Equipment replacement costs reaching millions of dollars
  • Extended power outages lasting days or weeks
  • Disruption to hospitals, water systems, and emergency services
  • Business interruption and economic losses
  • Environmental remediation expenses

What Is the Main Cause of Transformer Failure? The Critical Seven

1. Overloading: Pushing Beyond Design Limits

Transformers carrying more electrical load than designed for generate excessive heat that damages insulation and degrades cooling oil. Overloading beyond rated capacity leads to overheating, causing insulation materials to degrade and ultimately resulting in catastrophic failure.

Summer heat waves when air conditioners run constantly, or unexpected power demand spikes push transformers beyond safe operational thresholds. The damage compounds over time—a little overheating today, more tomorrow, until something breaks completely.

2. Insulation Breakdown: The Silent Killer

Insulation system failures rank as one of the main causes of transformer fire accidents, with materials intended to electrically separate windings and prevent short circuits deteriorating over time.

Multiple factors accelerate insulation degradation:

  • Water ingress from leaks
  • High temperatures accelerating aging
  • Electrical stress from voltage fluctuations
  • Chemical damage from contaminated oil
  • Physical damage during shipping or installation

When insulation breaks down due to moisture ingress, high temperatures, and electrical stress, it causes electrical arcing leading to explosions.

3. Lightning Strikes and Electrical Faults

Lightning strikes during storms damage transformer wiring and equipment, causing sudden voltage surges and overheating of insulation fluid. A single lightning bolt delivers millions of volts, overwhelming protective systems and creating massive internal arcing.

Other electrical faults include:

  • Animals causing short circuits
  • Voltage spikes from grid switching operations
  • Power surges from upstream equipment failures
  • Ground faults from damaged connections
  • Overvoltage conditions exceeding design specifications

4. Cooling System Failures

Transformer cooling systems like oil circulation or fans are crucial for dissipating heat, and their failure can cause the transformer to overheat and potentially explode.

Common cooling problems:

  • Pump failures stopping oil circulation
  • Clogged radiators reducing heat dissipation
  • Broken fans eliminating convective cooling
  • Oil leaks reducing coolant volume
  • Blocked passages preventing proper flow

Even a normally loaded transformer can reach dangerous temperatures within hours if cooling stops working.

5. Oil Contamination and Degradation

Contaminants such as dust, moisture, or metallic particles compromise the insulating properties of transformer oil, leading to electrical faults and ultimately explosions.

Fresh oil provides excellent insulation and cooling, but contamination allows electricity to arc at much lower voltages. Sources include:

  • Water from bad seals
  • Particles from degrading insulation
  • Carbon deposits from electrical arcing
  • Metal shavings from mechanical wear
  • Chemical breakdown as oil ages

6. Aging Infrastructure

Power transformers have limited operational lifespans, and as they age, the risk of failure increases, making regular maintenance and monitoring essential to prevent catastrophic events.

Many transformers operating today were installed 40-50 years ago. The electrical power system in the United States experienced its booming growth period from the early to mid-twentieth century, reaching a peak in 1973-1974, with large substation transformers now over forty years old and operating well past their service life expectancy.

Decades of daily heating and cooling cycles, constant electrical stress, weather exposure, vibration, and chemical breakdown make failure inevitable without proper maintenance and eventual replacement.

7. Mechanical Damage

Physical damage creates hot spots, loose connections, or compromised insulation that eventually leads to complete failure:

  • Earthquake damage
  • Severe weather impacts
  • Transportation accidents
  • Installation errors
  • Rust and corrosion
  • Internal component shifts during faults

Do Explosions Make Noise? Understanding the Acoustic Signature

Yes—transformer explosions make extremely loud noises distinguishable from other sounds. When fuses blow, they are extremely loud—often heard as a loud boom—and create a bright flash visible for miles.

The acoustic signature varies by failure type:

Major Explosions: Tank rupture produces a deep, powerful boom with sustained rumbling as burning oil ignites and pressure releases.

Fuse Operations: In most cases, the sound is not the actual transformer explosion but the transformer fuse blowing to prevent more catastrophic failure.

Arc Flash Events: Sharp cracking sounds from electrical discharge, similar to thunder but more concentrated and intense.

The sound carries far because:

  • High-pressure release creates powerful shockwaves
  • Arc flash produces supersonic expansion
  • Metal tank rupture generates concussive percussion
  • Burning oil creates sustained roaring

Electrical Failure Leads to Transformer Destruction: The Progression

Electrical failures—including poor insulation, over-voltage, static electrification, partial discharges, and power surges—can create intense electrical and thermal stresses within the transformer, leading to insulation breakdown and subsequent explosion.

The Millisecond Timeline of Catastrophe

Phase 1: Initial Fault (0-1ms) Something goes wrong—a loose connection, damaged insulation, dirty oil, or power surge creates extra heat or electrical arcing inside.

Phase 2: Oil Decomposition (1-10ms) Rising temperatures cause insulating oil to decompose and release flammable gases like hydrogen, methane, and acetylene, which become pressurized as liquid inertia prevents expansion.

Phase 3: Pressure Wave Propagation (10-50ms) Pressure differences between generated gas bubbles and surrounding liquid create shock waves that propagate and interact with tank structure, causing reflections that build up static pressure.

Phase 4: Static Pressure Buildup (50-200ms) Pressure waves bounce off metal walls, and accumulated pressure forces the metal to stretch and bend beyond elastic limits.

Phase 5: Catastrophic Rupture (200+ms) The tank can no longer contain the pressure. Violent rupture throws burning oil everywhere, releases toxic gases, and creates massive fire hazards.

Experimental data shows the entire process from arc initiation to depressurization can occur in as little as 19.7ms or up to 347ms, with an average of 116ms.

The Warning Signs Nobody Should Ignore

Transformers don’t explode without warning—they give clear signals weeks or months beforehand:

1. Rising Temperature Trends

Temperature increase typically appears first. Modern sensors detect these trends long before real damage occurs, identifying overload conditions, cooling system malfunctions, or developing internal faults.

2. Dissolved Gas Analysis (DGA)

Regular monitoring using hydrogen detection systems can help identify early fault conditions that often lead to explosions.

As problems develop, oil breakdown creates specific diagnostic gases:

  • Hydrogen: Partial discharge and corona
  • Methane: Low-temperature overheating
  • Ethylene: Medium-temperature problems
  • Acetylene: HIGH-ENERGY ARCING (critical warning)
  • Carbon monoxide/dioxide: Insulation degradation

One in three transformer failures occurs within 12 months of testing, highlighting why continuous online monitoring surpasses annual check-ups.

3. Partial Discharge Activity

Tiny electrical sparks in insulation gaps progressively damage materials until complete failure. Modern sensors detect and track these in real-time, providing advance warning.

4. Pressure Increases

Rising internal pressure indicates gas generation from heat or electrical problems. Early detection allows intervention before reaching dangerous levels.

5. Oil Quality Deterioration

Regular testing reveals chemical changes, water contamination, and particle accumulation. Bad oil accelerates insulation aging and reduces electrical stress tolerance.

6. Abnormal Sounds or Vibrations

Transformers normally hum steadily. Changes—buzzing, crackling, unusual vibrations—signal loose connections, core problems, or internal arcing.

Modern Technology That Prevents Explosions

Advanced Protection Systems

Transformer protection based on direct mechanical response of depressurization sets to tank inner dynamic pressure peaks can prevent explosions by releasing pressure before tank rupture.

These systems work by:

  • Bursting a rupture disc when pressure waves hit
  • Expelling oil and gas through controlled channels
  • Separating explosive gases and venting to safe areas
  • Injecting nitrogen to make the transformer safe for repairs

Technology used in car crumple zones—energy-absorbent tanks that deform rather than rupture—can prevent transformer explosions by absorbing pressure rises like modern vehicle design.

Continuous Monitoring Platforms

Real-Time Gas Monitoring: Systems continuously sample oil, detect gases as they form, and send data to central monitoring stations, watching 24/7 unlike annual testing.

Temperature Tracking: Advanced systems monitor oil temperature, winding temperature, and hot spots, catching cooling failures and overload conditions immediately.

Partial Discharge Detection: Special sensors identify electrical and acoustic signatures, assessing insulation condition and indicating when intervention is needed.

Pressure and Oil Level Sensors: Provide early warning of leaks, gas generation, and cooling problems, triggering alarms and automatic shutdown before pressure reaches dangerous levels.

Smart Analytics: Modern platforms use artificial intelligence to spot subtle patterns, predict failures, and recommend preventive actions.

Comprehensive Prevention Strategy

Proactive Measures That Work

1. Install Monitoring Systems Deploy online monitoring on all critical transformers. For less important equipment, establish regular testing schedules without long detection gaps.

2. Establish Clear Action Points Decide ahead: at what gas level do we investigate? At what temperature do we act? Don’t wait for catastrophic readings—respond to early warnings.

3. Maintain Consistently Preventive maintenance including cleaning, tightening connections, and replacing worn-out components is crucial in preventing premature failures.

Regular maintenance schedule:

  • Oil testing quarterly or monthly
  • Visual inspections for leaks and damage
  • Electrical insulation and winding testing
  • Cooling system checks and servicing
  • Electrical connection cleaning and tightening
  • Bushing inspection
  • Tap changer maintenance

4. Avoid Overloading Monitor load carefully, especially during peak demand. Implement procedures to reduce load before overheating becomes problematic.

5. Install Lightning Protection Installing lightning protection systems and proper grounding mitigates risks from lightning strikes and voltage surges.

6. Train Personnel Proper training for personnel working with transformers ensures they understand risks involved and follow safe operating procedures.

7. Plan Replacement Transformers don’t last forever. Budget for replacing aging equipment before failure, and maintain spare transformers when possible.

8. Use Quality Equipment Ensuring high-quality insulation materials and proper installation enhances transformer resilience against electrical failures.

Emergency Response: What to Do When a Transformer Explodes

Immediate Actions

If You’re Present:

Immediately evacuate to a safe area to avoid injury from debris or fire, and disconnect power if possible to prevent further damage.

Critical steps:

  1. Get away immediately – Keep at least 30 feet (10 meters) away—electricity can travel through ground or metal objects
  2. Call 911 – Report explosion location and any injuries
  3. Contact power company – They must shut down power to the area
  4. Evacuate others – Ensure nobody approaches the danger zone
  5. Avoid power lines – Stay 35+ feet from any downed wires

For Emergency Responders:

Transformer fires burn at temperatures between 1,760°F and 2,190°F for minimum four hours, requiring specialized firefighting approaches.

Special considerations:

  • Water alone often won’t extinguish oil fires
  • Special foam or powder systems work better
  • Mineral oil has fire and flash points around 330°F and 295°F respectively, creating significant pressure buildup when boiling
  • Electrical dangers remain until power is confirmed off
  • Toxic gas releases pose health hazards

Post-Explosion Protocol

Keep everyone away until declared safe, document everything for investigation, contain oil spills, and identify root causes to prevent recurrence on similar equipment.

Recovery Steps:

  1. Secure the perimeter
  2. Document all damage
  3. Contain environmental contamination
  4. Investigate failure cause
  5. Inspect similar transformers
  6. Implement corrective actions
  7. Restore power through alternative routes
  8. Replace damaged equipment

The Bottom Line: Prevention Is Everything

Power transformer explosions are serious events that can disrupt electricity supply, damage infrastructure, and pose risks to public safety, making prevention paramount for maintaining reliable power grids and ensuring safety.

Our infrastructure faces serious challenges: aging equipment, increasing power demands, climate change stressing systems in new ways, and pressure to reduce costs. In this environment, hoping transformers keep working isn’t a strategy—it’s wishful thinking.

Real-time monitoring and predictive maintenance aren’t optional extras anymore. They’re essential for responsible 21st-century operations.

Critical Questions Every Organization Must Answer:

  • Do we actually know our critical transformers’ current condition?
  • Would we receive warning if problems were developing?
  • Can we justify risking millions in losses to save thousands on monitoring?
  • How will we explain ignoring warning signs after an explosion happens?

The technology exists. The knowledge exists. Warning signs appear months before disaster strikes. The only remaining question: will we use these tools, or keep replacing transformers that didn’t have to fail?

Statistical Reality

Throughout a 20-year service life, 2.4% to 4% of all transformers should be expected to cause fires, with average annual major failure rates between 0.9% and 1.0%.

While relatively rare, the severity of consequences demands prioritizing prevention. Most failures result from problems developing over days, weeks, or months—providing ample opportunity for detection and intervention through proper monitoring.

Frequently Asked Questions

Q-1: Can monitoring really prevent all explosions? Yes, in most cases. Regular maintenance, advanced monitoring systems, and diligent upkeep of insulation and cooling systems are key to preventing transformer explosion incidents. Most failures stem from gradually worsening conditions detectable through continuous monitoring.

Q-2: What’s the most critical indicator to watch? Hydrogen appears first when oil breaks down, serving as an early warning. However, monitoring multiple gases provides the complete picture of transformer health.

Q-3: Who’s responsible for transformer safety? Power companies own and maintain transformers on utility poles and substations, while large industrial and commercial customers own transformers on their property and bear responsibility for maintenance and safety.

Q-4: Can damaged transformers be repaired after explosion? Usually not. Transformers that explode typically suffer catastrophic internal damage requiring complete replacement. However, minor failures caught early through monitoring can often be repaired economically.

Q-5: How long do fires burn after explosions? In real world conditions, hydrocarbon oil fires can last well over four hours before burning themselves out, requiring sustained firefighting efforts.

Remember: The warning signs are always there. The real question is whether anyone’s looking for them.